This page is an overview of the basic N5 Series, 3 kVA and 4 kVA. See the N5 Series listing for specific versions or contact sales via email, fax or voice to discuss configurations to meet your specific needs.
Model: ETI0001-N5 Series
3000 VA or 4000 VA
Rugged Rackmount Integrated UPS and
Power Distribution Unit Combination
ETI0001-N5, Navy Standard N5 Configuration, Rugged Power™
Isolated UPS, 3000 to 4000 VA Rugged Rack Mount UPS w/ Integrated
6 Circuit, 2 Pole, Intelligent, Solidstate Power Distribution Unit
Typical ETI0001-N5 Front Panel Layout w/ 2U Battery Module
Typical ETI0001-N5 Rear Panel Layout w/ 2U Battery Module
The field proven Rugged Systems™ UPS line is ideally suited for military, industrial, computer and telecommunications applications requiring high reliability, rugged construction, compact size and light weight design. These units are equally suited for use in shipboard, airborne, vehicular, field deployed or fixed locations with controlled or uncontrolled environments. The "N5 Series" was specifically designed to save rack space and installation costs while enhancing the functionality of both the UPS and PDU. The "N5 Series" does not require a separate PDU since the PDU functions are already integrated into the UPS module. This saves rack space, cabling and expense while improving overall reliability.
The heavy duty chassis occupy only 3U for the electronics module and 2U for the battery module of rack space while delivering up to 3000 or 4000 VA of clean, uninterruptible power. The rounded metal corners and rugged handles, both front and rear, aid in safe handling. The optional mounting kit includes flanges and legs for either horizontal or vertical positioning. Internally, all major components are well secured and electrically insulated to prevent damage due to shock and vibration. An internal transformer bay accommodates the input isolation transformer with provisions for both domestic and optional international voltages. The LED arrays keep the operator informed as to the unit's status including load and battery levels. The high intensity audible alarm can be heard in high noise environments, yet is easily adjustable to suit quieter conditions. All controls and protective devices are brought to the front panel with critical switches or breakers guarded. Further, all front panel devices are recessed to prevent damage or accidental operation.
The internal intelligent PDU allows control of the individual output circuits incorporating thermal and interlock interfaces for additional control and safety, plus Battleshort override. The display and control panel can be mounted remotely in the rack or on the front panel with only a logic level cable connection. The input circuit breaker and the galvanic isolation transformer all provide a double pole isolated source for all installations including shipboard systems or overseas locations where phase references and grounding are not consistent.
The rear panel provides locking connectors for the input and output power. A washable intake air filter and high capacity stainless steel ball bearing fans provide added protection in both controlled and hostile environments. Typically the exhaust air is diverted out the front vents, or easily changed to vent out the sides or both. The external battery connector allows the safe and easy addition of the standard or extra battery modules without having to shut the unit down. The batteries are maintenance free with immobilized electrolyte and are constructed of flame retardant materials. For more information, see the Battery Technology section. A frequency selection switch is available for those sites requiring 50 hertz output instead of the standard 60 hertz. The status D shell connector provides an interface with optional computer software providing loss of AC and low battery status as well as remote shut down capability.
See the Power Distribution Units section for a listing of stand alone PDUs. See the N3 Series UPS section for UPS without the integrated PDU and remote control.
Overall, the Rugged Power line is uniquely qualified for critical shipboard, vehicle, airborne or land based systems combining advanced modular design features with highly reliable construction
AC OUTPUT | |
Output voltage: | 120 VAC true sinewave standard, others optional |
Output rating: UPS | 3000 or 4000 VA in 3U chassis 0.65 to 0.75 pf std, optional configurations to 24,000 VA |
Non-linear load capacity: | Up to 100% non-linear load capability w/o derating |
Output voltage regulation: UPS | ± 3.0% static regulation of nominal ± 4.0% dynamic (0 to 50% load step) |
Overload surge capacity: | 110% for 10 minutes; 125% for 30 seconds |
Harmonic distortion: | Less than 5.0% into 100% non-linear load |
Output frequency: UPS | 60 or 50 Hz ± 2.5% synchronized to utility 60 or 50 Hz ± 1.0% w/ utility not available |
Operational status | Status, load and battery level LEDs, w/contacts Adjustable level,+90 dB audible alarm w/on/off |
AC INPUT | |
Input voltage selection: | Nominal 115 VAC, optional autoranging input of 85-270 VAC |
Input voltage tolerance: UPS | 85-135 VAC @ full load without using battery, to 70 VAC @ 75% load |
Input frequency: | From 46 Hz to 70 Hz standard, optional to 440 Hz |
Input/output isolation: | Up to 4000 VA, up to 120 dB common mode, <5 mA leakage |
Input transient suppression: | Complies with IEEE 587 and UL 1449 |
Input control/protection: | Guarded 2 pole input breaker w/ UPS fuse Optional cold start to turn on w/o AC present |
Input power connection: | AMP CPC Type XII locking, various options |
BATTERY | |
Battery type: | Maintenance free immobilized electrolyte, Flame retardant materials, Oxygen Index 28+ |
Battery life: | Rated for continuous service life of 5 years |
DC protection: | Panel mounted fuses standard, optional breaker |
Battery expansion: | Up to 24 hours w/ Battery Expansion Modules |
DISTRIBUTION PANEL | |
Output circuits: | Six controlled outputs via solidstate relays |
Output control: | Local/remote control panel w/rocker switches Thermal and remote interlock ON/OFF control |
Output receptacles: | IEC320-15R w/cord restraints, various options |
MECHANICAL | |
Dimensions ( H x D x W ): UPS 2U Battery Module (standard) 3U Battery Module (optional) |
5.25 (3U) x 23.5 x 19.0 in (133 x 597 x 483 mm) 3.50 (2U) x 23.5 x 19.0 in ( 89 x 597 x 483 mm) 5.25 (3U) x 23.5 x 19.0 in (133 x 597 x 483 mm) |
Rack Slide Mount Patterns: | Jonathan, General Devices patterns standard, others optional |
Alternate Mounting Options: | Table, Wall, Floor, Portable, Horizontal/Vertical |
Unit weight: UPS 2U Battery Module (standard) 3U Battery Module (optional) |
95 lb. ( 43 kg) with lift handles front and rear 102 lb. ( 46 kg) with lift handles front and rear 150 lb. (102 kg) with lift handles front and rear |
Audible noise: | Less than 47 dB @ 5.0 ft., ANSI "A" scale |
Cooling type: | High capacity, positive pressure, forced air |
Cooling air direction: | Rear intake, exhaust to front or sides or both |
Air intake filter: | Washable filter media, various porosities |
ENVIRONMENTAL | |
Storage temperature: | -40° to 158° F ambient (-40° to 70° C) with fully charged batteries |
Operating temperature: | 32° to 113° F ambient (0° to 45° C ), lower/higher optional |
Operating humidity: | 0 to 95% relative humidity (non-condensing) |
Storage elevation: | Up to 40,000 ft (12,192 m) |
Operating elevation: | Up to 15,000 ft (4,572 m), higher optionally |
STANDARDS | |
United States: | Meets UL-1778 standard for UPS equipment, |
Canada: | CSA C22.2 No. 107 UPS safety requirements |
EMI Protection: | EMI/RFI FCC Part 15, Class A standard, MIL STD 461 optional |
OPTIONAL ACCESSORIES | |
Autoranging International Input, Cold Start, Alternate I/O Configurations, Dual Source Input, Battery Expansion, Batteryless Operation, Battery Charger/Conditioner, Power Distribution Units, Software Interface, 10BaseT Ethernet SNMP/HTTP port, Transport Cases |
This page was last modified on: March 18, 2012